Vendor:
Adlink’s NuDAM data acquisition modules make up a total acquisition network and control system.
Up to 256 NuDAM modules can be remotely controlled on any RS-485 network from a host computer, via a single serial RS-232, allowing communication from as far as 4000 feet from the host.
Based on the RS-485 multi-drop network system, each module has a unique address ID, whereby simple ASCII command & response protocols through the standard RS-485 interface can control all the NuDAM modules in the RS-485 network.
The NuDAM modules provide direct communications with a wide variety of sensors, perform all signal conditioning, scaling, linearization and conversion, and can acquire measurements of temperature, pressure, flow, voltage, current, and multiple digital signal types.
| Technical specifications | |
|
Interface |
|
|---|---|
| Interface | RS-485, 2 wires |
| Speed (bps) | 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K (115.2K is only for firmware revision above A4.00) |
|
Digital Input |
|
| Channels | 4 |
| Common External Voltage | +24 V |
| Current Limit Resistor | 2.2 kΩ |
| Isolation Voltage | 5000 VRMS |
| Input Type | Dry contact |
| Input polarity | Programmable |
|
Relay Output |
|
| Channels | 4 |
| Output Type | 2x form C and 2x form A |
| Contact Rating | AC: 0.5 A / 125 V; DC: 1 A / 30 V, 0.3 A / 110 V |
| ON/OFF Interval Time | 3 ms |
| Internal Insulation Resistance | 1000 MΩ @ 500 VDC |
| Breakdown voltage | 750 Vrms(between open contact), 1000 Vrms(between contact and coil) |
| Expected Life | 20 000 times (1 A 30 VDC resistive at 20 cpm) |
| Output polarity | Programmable |
| Output power on/safety state | Programmable |
|
Watchdog Function |
|
| Module internal watchdog timer | 150 ms |
| Power failure threshold | 4.65 V |
| Safety value | 4 output channels |
| Host programmable watchdog | 100 ms ~ 25.5 sec |
|
Power |
|
| Power supply | +10V to +30V |
| Power consumption | 0.84 W |
| Model | Description |
| ND‑6060 | Relay Output & Digital Input Module |
Loading data...